Search
`
November 25, 2024

MRC Approvals 5/30/13: PMU Costs, CFTC Order, UTC Credit

Below is a summary of problem statements and manual, Operating Agreement and Tariff changes approved by the Markets and Reliability Committee Thursday, May 30, 2013.

PMU Deployment

The committee endorsed manual revisions requiring new gen­er­a­tors to pay for the instal­la­tion of pha­sor mea­sure­ment units (PMUs). There were four no votes and three abstentions. The Planning Committee approved the changes March 7, reject­ing an alter­nate pro­posal to have PJM cover the cost.

Rea­son for change: PMU data can enhance grid reli­a­bil­ity for both real-time oper­a­tions and plan­ning appli­ca­tions (e.g., gen­er­a­tion dynamic model cal­i­bra­tion and val­i­da­tion, pri­mary fre­quency response, oscil­la­tion mon­i­tor­ing and detec­tion). PJM expects to receive PMU data from 82 sub­sta­tions by the end of 2013 but has none located at gen­er­a­tion stations.

Impact: The Inter­con­nec­tion Ser­vice Agree­ment will be changed to require instal­la­tion of PMUs at new inter­con­nec­tions for gen­er­a­tors with name­plate rat­ings of 100MVA or larger.  Data col­lected by the PMU must be trans­mit­ted to PJM con­tin­u­ously and stored locally for 30 days.

Commodity Futures Trading Commission Exemption Order

MRC and the Members Committee approved changes to the Operating Agreement and Tariff to comply with conditions in the Com­mod­ity Futures Trad­ing Com­mis­sion order exempt­ing most PJM mar­ket par­tic­i­pants from CFTC jurisdiction.

Rea­son for Change: The CFTC agreed March 28 to largely exempt from its reg­u­la­tions Finan­cial Trans­mis­sion Rights, day ahead and real time energy trans­ac­tions, for­ward capac­ity trans­ac­tions and reserve reg­u­la­tion trans­ac­tions, sales that are already reg­u­lated by the Fed­eral Energy Reg­u­la­tory Com­mis­sion.

How­ever, the CFTC said the exemp­tion did not apply to finan­cial mar­ket par­tic­i­pants that can­not qual­ify as “appro­pri­ate per­sons” under the Com­mod­ity Exchange Act (CEA). PJM responded April 7 by announc­ing it may deny trad­ing priv­i­leges to small mar­ket par­tic­i­pants if they are unable to qual­ify for the exemp­tion.

Impact: The changes approved Thursday expand finan­cial mar­keters’ offi­cer cer­ti­fi­ca­tion requirements. Although the changes require FERC approval, PJM CFO Suzanne Daugherty said her staff will immediately begin contacting about 100 market participants for whom the RTO does not have sufficient financial information.

The MRC was asked to choose between two options regarding the financial qualifications of an unlimited guarantor.

Stephanie Staska, of Twin Cities Power LLC, proposed language requiring “an issuer that has at least $1 million of total net worth or $5 million of total assets per Participant for which the issuer has issued an unlimited Corporate Guaranty.”

PJM proposed that the guarantor be “an issuer that would qualify for an Unsecured Credit Allowance of at least $1 million.”

Daugherty said the Twin Cities language complied with the CFTC order but was “just a little less thorough” than PJM’s proposal.

Staska said her proposal was identical to that used by MISO for compliance with FERC order 741. “It “does just as much to protect the market,” she said.

The changes were approved with the Twin Cities language with no objections and three abstentions.

See, “CFTC Approves Dodd-Frank Exemption for RTOs,” “PJM May Bar Some Financial Players from Trading.”

Up-To Congestion (UTC) Transaction Credit Requirements

MRC and the Members Committee endorsed credit requirements for up-to-congestion (UTC) trades, a fast-growing virtual transaction that previously had no credit requirements.

Rea­son for Change: UTC trad­ing vol­umes have grown dra­mat­i­cally since 2010 but there are no credit require­ments to pro­tect mar­ket par­tic­i­pants against defaults.

Impact: Bid screen and cleared port­fo­lio credit require­ments are based on a per­centile of the dif­fer­ence between each member’s bid or cleared price and the two-month rolling aver­age of real-time value per path.

Traders who fail the credit screen based on their initial bids will be able to rebid within their limits.

See “MIC OKs UTC Credit Requirement.”

FTR Forfeiture Rule Changes

MRC approved a man­ual change doc­u­ment­ing the Market Monitor’s cur­rent appli­ca­tion of the FTR forfeiture rule on incre­ment and decre­ment transactions and a prob­lem state­ment to deter­mine how the rule should be inter­preted in the future.

Reason for Change: PJM dis­cov­ered only recently that it dis­agreed with the cri­te­ria by which the mon­i­tor has been deter­min­ing whether a company’s vir­tual bid is “at or near” the deliv­ery or receipt buses of its FTR.

Impact: The manual change documents the monitor’s interpretation of the rule. The inquiry may result in changes to the application of the rule.

The mon­i­tor has been apply­ing the penalty based on the net impact of vir­tual bids, trig­ger­ing its appli­ca­tion in less than one-tenth of 1% of trades. PJM pro­posed a dif­fer­ent cal­cu­la­tion under which com­pa­nies would lose any profit for an FTR if 75% or more of the energy injected or with­drawn by a vir­tual bid is reflected in a con­strained path between FTR source and sink.

“We believe this is about as clear as we can make it,” Stu Bresler, PJM vice president of market operations, said of the manual change.

The problem statement was approved over the objections of 15 members of the PJM Public Power Coalition.

“There are at least five new problem statements on this week’s agenda,” said Bill Schofield, of Customized Energy Solutions, which represents the coalition. “This is not the time to be adding this to our plate.”

But representatives of financial marketers said revising the rule was important to them.

“Because of the heightened risk in terms of FERC enforcement action … I think it’s important that we get some clarity on how we analyze these power flows,” said Greg Pakela of DTE Energy Trading. “This kind of acts as a safe harbor.”

FTRs are “a fundamental building block to the forward price curve,” said Bruce Bleiweis, of DC Energy, LLC. “Many people would like some additional clarity here.”

Market Monitor Joseph Bowring also supported the review, noting that the rule has been unchanged since 2001. “Are we getting false positives or false negatives?” he asked. “We need to make sure everyone understands the rule. I think there’s a lot of misunderstanding.”

See “Back to the Drawing Board on FTR Forfeitures For Incs, Decs.”

Energy Market Uplift Costs

MRC approved a prob­lem state­ment cre­ating a senior task force to take a broad review of its method of pro­vid­ing Oper­at­ing Reserve pay­ments.

Reason for Change: PJM said changes are needed to reduce grow­ing uplift costs. Oper­at­ing Reserves are “make whole” pay­ments that ensure gen­er­a­tors dis­patched out of merit for sys­tem reli­a­bil­ity don’t oper­ate at a loss. Because they are col­lected through uplift charges and not reflected in day-ahead or real-time loca­tional mar­ginal prices, they can­not be hedged.

Impact: The task force will consider revising the sources of Operating Reserve charges and the methodology used to allocate them. The goal will be to minimize uplift costs while ensuring market prices are consistent with operational reliability, decrease charge rates, and reduce transaction risk due to variable fees.

See “PJM Proposes Operating Reserve Changes to Cut Uplift.”

PJM, FERC Rules Buffet EnerNOC

With its reliance on demand response and heavy concentration in PJM, EnerNOC has seen its fortunes wax and wane based on decisions made in Valley Forge and Washington. The company cited the following examples in its 10-K disclosures to shareholders:

  • The company saw its DR revenues fall in 2011 versus 2010 due in part to lower prices in the PJM, New York and New England markets and fewer demand response events in PJM during the year, which cut energy payments.
  • The Federal Energy Regulatory Commission’s February 2012 order accepting a PJM proposal on measuring and verifying DR capacity hurt the company’s revenues and profit margins.
  • PJM’s elimination of its Interruptible Load for Reliability (ILR) program last June “reduced the flexibility that we had to manage our portfolio of demand response capacity in the PJM market and impacted our revenues and profit margins.”
  • Declining PJM capacity market prices hurt revenues, gross profits and profit margins in 2012. “To the extent we are subject to other similar price reductions in the future, our revenues, gross profits and profit margins could be further negatively impacted.”

East Kentucky Power Cooperative System Joins PJM

PJM system operators took over management of the East Kentucky Power Cooperative system at midnight Saturday, adding almost 3,100 MW of generation and 2,800 miles of transmission to the RTO.

While PJM is a summer-peaking system, EKPC’s demand peaks in the winter. “The diversity of demand between EKPC and other PJM members and the resources they bring will strengthen reliability and have economic benefits not only for EKPC but throughout the region we serve,” said PJM President and CEO Terry Boston.

EKPC-map-chartEast Ken­tucky, which joined PJM as an Other Sup­plier in 2005, esti­mates it will save almost $132 mil­lion over the next decade by tak­ing advan­tage of PJM’s economies of scale and gen­er­a­tion diversity.

“Our organizations have put a lot of hard work into this integration,” EKPC CEO Anthony “Tony” Campbell said in a statement. “This move will help EKPC to operate more efficiently and economically.”

The biggest sav­ings will come from reduced reserve require­ments. East Ken­tucky main­tains a 12% reserve mar­gin. By join­ing the summer-peaking PJM, it will be able to reduce its reserve to 2.8%, allow­ing it to sell the dif­fer­ence in the capac­ity market. The inte­gra­tion also will result in more eco­nom­i­cal gen­er­a­tion dis­patch, as the coop replaces its higher cost gen­er­a­tion with cheaper PJM power.

East Ken­tucky said its move was prompted by increas­ing trans­mis­sion con­straints with poten­tial coun­ter­par­ties and fed­eral envi­ron­men­tal reg­u­la­tions, which made it expen­sive to con­tinue oper­at­ing as an inde­pen­dent con­trol area and bal­anc­ing author­ity. The coop has inter­con­nec­tions with TVA, Duke Energy, Amer­i­can Elec­tric Power and Louisville Gas and Elec­tric Co./Kentucky Util­i­ties Co.

EKPC is owned by 16 distribution cooperatives that serve 1.1 million people in 87 counties across Kentucky.

PJM, Monitor Push New MOPR Changes

Andy Ott and Joseph Bowring often disagree.

But last week, PJM’s Senior Vice President for markets and the Independent Market Monitor said there’s at least one thing on which they agree: the MOPR unit-specific review process is “flawed, non-transparent and provide[s] too much discretion to PJM and the IMM.”

The Markets and Reliability Committee approved a problem statement Thursday to standardize and improve the transparency of the unit-specific review process used in applying the Minimum Offer Price Rule (MOPR).

PJM and the monitor wanted to do away with the unit-specific MOPR exemptions in favor of blanket exemptions for win­ners of com­pet­i­tive solicitations and self-supply resources.

But the Federal Energy Regulatory Commission ruled May 2 (ER13-535) that elim­i­nat­ing the review for gen­er­a­tors that don’t meet the exemp­tions was not just and reasonable. Instead, FERC suggested that PJM conduct a stakeholder process to consider revisions to the process. (See “Split Decision on MOPR.”)

MOPR was added to PJM’s capac­ity mar­ket rules in 2006 to pre­vent buyer-side mar­ket power.

The problem statement and issue charge approved by MRC seeks to develop new financial modeling assumptions, with a goal of standardizing them and making them more consistent with those used to establish Net CONE (cost of new entry). Among the issues to be considered are asset life and calculations of net revenue and cost of capital.

The project, to be assigned to the Capacity Senior Task Force, is scheduled for completion in time for a December 1 FERC filing and implementation in the 2014/15 delivery year.

Compliance Filing

Ott also briefed the MRC on a compliance filing the RTO must make in response to the FERC order.

PJM’s response, filed yesterday:

  • allows MOPR exemp­tions for qualifying facilities under con­tract to capac­ity mar­ket sellers;
  • pledges to review the net short and net long thresholds for the self-supply exemption every four years; and
  • defines “repow­er­ing” to clar­ify that it includes both projects that increase capac­ity and those that don’t. PJM had pro­posed that repow­ered gas gen­er­a­tors be treated as a new resource under MOPR.

Also yesterday, Calpine Corp., FirstEnergy Corp. and NRG Energy Inc. filed requests asking FERC to reconsider its ruling, joining a rehearing request filed last week by the Illinois Commerce Commission.

The Illinois filing alleges FERC erred in allowing PJM to subject integrated gasification combined cycle (IGCC) generators to MOPR.

Calpine Corp said FERC was mistaken in requiring PJM to retain the unit-specific review. The commission “neglected to address the fact that the MOPR modifications set forth in the December 7 Filing were proposed as a package that was overwhelmingly approved by stakeholders and that reflected significant compromises on the part of Calpine and other parties,” Calpine said.

FirstEnergy said the self-supply exemption is based on PJM’s analysis of the 2015/2016 auction, which it said is not representative of current market conditions. The company said FERC should address the potential that the exemption could be gamed.

NRG said the commission had abandoned its long-standing “regulatory compact” with investors. “The MOPR Order cuts the legs out from under the buyer-side power mitigation rules by selectively approving the elements of the PJM proposal that would weaken the MOPR, while rejecting those elements that would strengthen the buyer-side market power protections,” the company said.

MRC Meeting Preview: PMU Costs, CFTC Order, UTC Credit

erators to pay for the installation of phasor measurement units (PMUs).

The Planning Committee approved the changes March 7, rejecting an alternate proposal to have PJM cover the cost. PMU data can enhance grid reliability for both real-time operations and planning applications.

Planning Committee Votes to Bill Generators for PMUs
3. Commodity Futures Trading Commission (CFTC) Exemption Order (9:25-9:55)
The committee will be asked to endorse the changes to the Operating Agreement and Tariff to comply with conditions in the Commodity Futures Trading Commission order exempting most PJM market participants from CFTC jurisdiction.

The CFTC agreed March 28 to largely exempt from its regulations Financial Transmission Rights, day ahead and real time energy transactions, forward capacity transactions and reserve regulation transactions, sales that are already regulated by the Federal Energy Regulatory Commission. However, the CFTC said the exemption did not apply to financial market participants that cannot qualify as “appropriate persons” under the Commodity Exchange Act (CEA). PJM responded April 7 by announcing it may deny trading privileges to as many as 55 small market participants if they are unable to qualify for the exemption. PJM said the change was necessary for the RTO to avoid being deemed a swap dealer and becoming subject to CFTC reporting requirements.

The changes being considered expand financial marketers’ officer certification requirements.

PJM Delays Action on CFTC Order

CFTC Approves Dodd-Frank Exemption for RTOs

PJM May Bar Some Financial Players from Trading
4. Up-To Congestion (UTC) Transaction Credit Requirements (9:55-10:10)
The committee will be asked to endorse credit requirements for up-to-congestion (UTC) transactions.

UTC trading volumes have grown dramatically since 2010 but there are no credit requirements to protect market participants against defaults. Bid screen and cleared portfolio credit requirements are based on a percentile of the difference between each member’s bid or cleared price and the two-month rolling average of real-time value per path.

MIC OKs UTC Credit Requirement
5. PJM Manuals (10:10-10:30)
The committee will be asked to approve the following manual revisions:

A. Electronic Notifications for Curtailment Service Providers: Changes to Manuals 1 and 18 will implement an automated process that will allow Curtailment Service Providers to provide operational data to — and receive dispatch instructions from — PJM. The new Load Response System (eLRS) process replaces the current manual methods, which rely on email and spreadsheets.

Manual Changes to Implement Electronic Notification System

B. Residual Zone Pricing: Residual Zone Pricing will replace physical zone LMPs for real-time load effective June 1, 2015. A Residual Zone is an aggregate of all load buses in the physical zone, excluding load priced at nodal locations. The change was endorsed by the Members Committee in February 2012 and approved by FERC in Docket ER13-347.

Manual, Tariff Changes: Residual Zones, EKPC, Loss of Internet, Regulation Market

C. East Kentucky Power Cooperative: PJM needs to add the East Kentucky Power Cooperative zone into PJM markets manuals to accommodate the coop’s integration into PJM effective June 1.

Manual, Tariff Changes: Residual Zones, EKPC, Loss of Internet, Regulation Market

D. NERC Reliability Standards: PJM needs to amend M-36: System Restoration to reflect NERC Standards EOP-005-2 (System Restoration Plans) and EOP-006-2 (Reliability Coordination – System Restoration).  Updates for consistency with other RTOs; updates underfrequency load shed tables; incorporates recommendations from RFC/SERC audit, and adds specific references to transmission operator restoration plans.

E. Manual 03A:  Energy Management System (EMS) Model Updates and Quality Assurance:
The changes include numerous edits for updates and clarity.

Manual 03: Transmission Operations

F. Regulation Market Cost-Based Offers:  New rules implemented in October require regulation offers to include capability (cost, in $/MWh to reserve a resource for regulation) and performance (costs of tracking the regulation signal in miles/MW).  Previous rules, as defined in Manual 15, did not include performance costs.

Manual, Tariff Changes: Residual Zones, EKPC, Loss of Internet, Regulation Market

G. Manual 35: Definitions and Acronyms: Adds language to Economic Maximum and Economic Minimum definitions; changed Operations Analysis Working Group to Operations Assessment Working Group; Replaced TTV4TF (TO/TOP Version 4 Task Force) with TTMS (TO/TOP Matrix Subcommittee).

H. NERC standard PRC-023-2: Updates to Manual 14B: PJM Region Transmission Planning Process are required to implement standard PRC-023-2 (Transmission Relay Loadability). PJM annually develops transmission facility list to comply with NERC criteria.

I. Manual 03: Transmission Operations: Semi-annual update to incorporate procedural changes.
Recess (10:30-11:15)
The MRC will recess for a brief Members Committee meeting to finalize revisions to the OA and Tariff regarding the CFTC Exemption Order and the UTC credit requirements (#s 3 and 4 above).
6. FTR Forfeiture Rule Changes (11:15-11:30)
MRC will be asked to approve a manual change documenting the Market Monitor’s current application of the FTR forfeiture rule on increment and decrement transactions and a problem statement to determine how the rule should be interpreted in the future.

PJM discovered only recently that it disagreed with the criteria by which the monitor has been determining whether a company’s virtual bid is “at or near” the delivery or receipt buses of its FTR.

The monitor has been applying the penalty based on the net impact of virtual bids, triggering its application in less than one-tenth of 1% of trades. PJM proposed a different calculation under which companies would lose any profit for an FTR if 75% or more of the energy injected or withdrawn by a virtual bid is reflected in a constrained path between FTR source and sink.

Back to the Drawing Board on FTR Forfeitures For Incs, Decs
7. Energy Market Uplift Costs (11:30-11:45)
MRC will be asked to vote on a proposed problem statement that would create a senior task force to take a broad review of its method of providing Operating Reserve payments. PJM said changes are needed to reduce growing uplift costs.

Operating Reserves are “make whole” payments that ensure generators dispatched out of merit for system reliability don’t operate at a loss. Because they are collected through uplift charges and not reflected in day-ahead or real-time locational marginal prices, they cannot be hedged.

PJM Proposes Operating Reserve Changes to Cut Uplift
8. Minimum Offer Price Rule (MOPR) Compliance Filing (11:45-12:00)
PJM will provide a summary of PJM’s compliance filing in response to FERC’s May 2 order on the Minimum Offer Price Rule (ER13-535). FERC allowed PJM to exempt two categories of resources from MOPR but denied its request to eliminate its current unit-specific review.

Split Decision on MOPR
First Readings:
9. MOPR Unit Specific Exemption (12:45-1:00)

10. FTR Modeling Proposals (1:00-1:30)

11. Suspension of Day-Ahead Market for Loss of Internet (1:30-1:45)

12. Regional Planning Process Task Force (RPPTF) (1:45-2:15)

13. Demand Response Problem Statement (2:15-2:30)

14. Gas Electric Senior Task Force (GESTF) (2:30-2:45)

15. Tariff and OA Errata (2:45-3:00)

16. Replacement Capacity (3:00-3:15)

17. Transparency of TO Calculations (3:15-3:30)

18. PJM Manuals (3:30-3:45)
Future Agenda Items (3:45)]>

“Multi-Driver” Transmission Proposal Challenged – UPDATE

Two utilities last week signaled their intent to oppose a proposed “multi-driver” approach for incorporating public policy goals in PJM’s transmission planning process.

Representatives of Public Service Electric and Gas Co. and Rockland Electric Co. objected at a teleconference Wednesday of the Regional Planning Process Task Force when participants were asked if there were anyone who “couldn’t live with” the multi-driver proposal.

In a non-binding poll May 14, 112 of 128 task force participants (88%) said they favored the multi-driver approach, which would integrate public policy requirements into PJM’s existing reliability and market efficiency analyses for transmission improvements. 85% of those participating said public policy upgrades should be allocated only the incremental costs they add to an identified reliability or market efficiency project.

Because of the utilities’ objections Wednesday, the task force was not able to claim a Tier 1 consensus and will schedule a formal vote to determine its recommendation to the Markets and Reliability Committee. As a result, the issue will not go to a first reading in the MRC until at least June 27.

Order 1000 Compliance

To require public policy transmission improvements to be funded only as standalone projects would result in unnecessary expense, said Walter Hall, of the Maryland Public Service Commission.  “If PJM doesn’t develop a rational approach [to public policy requirements] they will find themselves very quickly in violation of FERC [Order 1000] requirements,” he said. “… I really think we need more from these two objectors as to how to move forward.”

PSEG noted that FERC did not require PJM to incorporate the multi-driver approach.

In its Order 1000 compliance filing Oct. 25, PJM said it was committed to developing the multi-driver approach.  The RTO said it may allow “greater flexibility in developing more efficient and cost-effective projects that could include a combination of public policy components and reliability and/or economic components.”

Some commenters told FERC that PJM’s filing was not compliant with Order 1000 without a multi-driver approach.  AEP said PJM’s planning process does not credit proposals that more efficiently address multiple benefits because the planning process looks for solutions that solve individual needs. As a result, AEP said, projects that provide greater multi-driver benefits may be rejected in favor of a project that has a greater impact on only reliability.

FERC Won’t Force Multi-Driver

In its March 22 ruling on PJM’s compliance filing, FERC noted PJM’s commitment to developing the multi-driver approach and encouraged PJM and its stakeholders to “explore future enhancements to improve the regional transmission planning process.”

However, it ruled that the multi-driver approach was not required to meet Order 1000. “PJM has integrated consideration of transmission needs driven by public policy requirements into is transmission planning process by incorporating those needs into the sensitivity studies, modeling assumption variations and scenario planning analyses,” the commission wrote.

Benefit Determination, “Upgrade” Definition

The task force also received the results of a vote on how to determine benefits for regional market efficiency projects. 87% of respondents favored a proposal to calculate benefits on a 50/50 ratio based on its impact on production costs and net load payments (energy benefits) or impact on capacity costs and net capacity payments (capacity benefits). Only 29% favored continuing the current method, under which 70% of benefits are calculated based on production or capacity cost savings.

The task force also is developing a revised definition of trans­mis­sion reli­a­bil­ity “upgrades” in response to the March 22 FERC ruling. (See “PJM’s ‘To Do’ List.”)

Order 1000 reserved con­struc­tion of trans­mis­sion reli­a­bil­ity upgrades — which it defined as includ­ing tower change outs and recon­duc­tor­ing — to incum­bent util­i­ties. The com­mis­sion said PJM’s OATT and agree­ments con­tain ref­er­ences to sev­eral types of upgrades and it is unclear which PJM intends to include in the Order 1000 definition.

For combinations of new and existing transmission lines, PJM’s proposal would differentiate based on the following criteria:

  • For lines shorter than 20 miles, the entire project is an upgrade only if the new line segment is less than 50% of total transmission line length.
  • For lines 20 miles or longer the entire project is an upgrade if the new line segment is either less than 10 miles or less than 10% of the total transmission line length. For example, on an existing 120-mile line, an addition of 10.1 miles would be considered an upgrade because — although it is longer than 10 miles — it is less than 10% of the original length. An addition of 13 miles would be considered a new project because it is both longer than 10 miles and greater than 10% of the original length.  

NERC Urges Planners to Incorporate Gas Risk

The North American Electric Reliability Corp. urged electric industry planners Wednesday to begin incorporating the risk of natural gas supply interruptions in their reliability and resource assessments.

In its second major report on the growing interdependence between the natural gas and electric industries, NERC also identified gas-related reliability risks and mitigation strategies and recommended increased communication and coordination between the two industries.

“Resource planning and adequacy assessments in some areas do not fully account for the risk of disruptions in the natural gas and other fuel supply chains,” NERC wrote, noting that such assessments typically assume the availability of fuel.

Trends

NERC noted that natural gas has risen from 17% to 25% of electric generation over the past decade and is projected to provide 50% of peak demand by 2015. At the same time, natural gas demand from transportation, manufacturing and exports is also expected to increase.

Unlike fuel oil and coal, natural gas is not easily stored on-site, meaning that generators must rely on just-in-time deliveries.

Most gas peaking units and many intermediate and baseload units have interruptible gas transportation contracts, leaving them increasingly vulnerable to interruptions during times of peak gas demand.

power-and-non-power-gas-demand-vs.-temperature
Non-Power & Power Gas Demand as a Function of Temperature (Source: NERC)

In NERC regions reporting such data, about 58% of gas‐fired capacity has firm supply. PJM reported that all of its dual-fuel generators and less than half of its other gas-fired units had firm fuel transportation contracts.

“As gas consumption for both power and non‐power uses has grown, the availability of interruptible capacity has declined, especially during periods of peak gas demand,” NERC said. “… Although generators may have contractual obligations to perform, performance incentives, particularly in competitive wholesale electricity markets, may not be strong enough to incentivize generators to procure firm or otherwise reliable fuel supplies.”

History of Interruptions

Using its Generator Availability Data System (GADS), NERC identified 1,240 cases over the last 10 years in which gas-fired generators reported outages due to lack of fuel. Almost half of the incidents occurred in the Reliability First Corp. (RFC) territory, which includes most of PJM.

Regions reported average lost capacity of 96 MW to 140 MW and outage lengths of 5½ hours (Florida Reliability Coordinating Council) to 47 hours (RFC).

The report summarizes several notable incidents, including February 2011, when the Southwest suffered rolling blackouts and major gas curtailments as a result of extreme cold. More than 250 electric generating units experienced outages totaling 1.2 TWh.

The 2011 incident also exposed the gas industry’s dependence on electricity: While most gas curtailments were the result of wellhead freeze‐offs, more than a quarter of the lost gas supply was due to the loss of electric pumping units or compressors.

Vulnerabilities

Gas-fired generators are vulnerable not only to supply interruptions but also to reduced pipeline pressure, which can persist even after gas starts flowing again.  NERC said critical gas generators should consider on‐site booster compression to improve reliability.

Generators also require consistent gas quality. Gas with a high British thermal unit (Btu) level from high ethane, or propane compositions can burn too hot in low‐nitrogen oxide (NOx) burners. “In cases where a number of gas‐fired units obtain their fuel from the same pipelines, changes in natural gas heat content can result in multiple unit trips at nearly the same time,” NERC said.

Risk-based Approach Needed

NERC recommended planners begin conducting a “three-layer” analysis of regional interdependencies and risks.

Layer 1 would require PJM and other system operators to compare their gas load for various weather conditions to the capacity of their gas infrastructure under normal operating conditions.

In Layer 2, the same gas load duration curves are compared to gas infrastructure capacity under contingencies, such as a compressor station outage or mainline capacity reduction.

NERC outlined such a scenario for a pipeline serving six gas-fired generators totaling 3,500 MW. The loss of all primary and backup compressors at a compressor station on the line would result in loss of all 3,500 MW within 110 minutes. Under the line break scenario, gas flow would be eliminated, resulting in a loss of all generation in about 16 minutes.

Line-break-scenario
Line Break Scenario (Source: NERC)

The final step in the three-layer scheme is the performance of a Monte Carlo analysis to provide a probabilistic assessment on how often gas-fired generators would lose fuel under a wide range of weather and gas supply conditions.

Such analyses requires good data, but the gas industry has no comprehensive statistics on interruptions similar to NERC’s GADS data on generators. As a result, gas outage data would have to be estimated from several sources, including pipeline bulletin boards, accident reports filed with government agencies and industry surveys.

Operational and resource planning implications

NERC also recommended increased training of pipeline and electric system operators to enhance cross-industry understanding and information sharing. NERC said electric Balancing Authorities and Reliability Coordinators may not “have an adequate understanding” of the information available to them under FERC order 587, which requires gas pipelines to post information on issues such as capacity constraints, gas quality warnings and scheduled maintenance.

“While the generators’ fuel managers may understand the critical and non-critical notices the information may not be readily communicated or understood well enough by the BAs or RCs,” NERC said.

Electric “operational procedures should include formalized coordination with the gas supply and pipeline industry, as well as emergency procedures during extreme events,” NERC said.

Dual Fuel

About 125 GW of gas‐fired generation, 35% of gas capacity under NERC jurisdiction, has dual‐fuel capabilities. NERC said state and federal environmental agencies should consider relaxing rules regulating backup oil use and emissions to maximize the flexibility of such units.

Capacity Auction: New Generation, Imports Up, Prices, DR Down – UPDATE

By Rich Heidorn Jr.

New gas-fired generation and a near doubling of imports caused a big price drop in PJM’s annual capacity auction, the RTO announced late Friday.

Prices ranged from $59 to $119/MW-day — down 29% to 68% — in most of PJM, although the Public Service Electric and Gas. Co. Locational Deliverability Area saw a 31% rise to $219.

More than 169,000 MW of unforced capacity was acquired for the 2016-2017 planning year, giving the RTO a projected reserve margin of 21.1%.

BRA Clearing Prices in the RTO (Source: PJM Interconnection, LLC)
(Source: PJM Interconnection, LLC)

“Prices were generally lower than last year’s auction due to competition from new, gas-fired generation, low growth in demand because of the slow economy and increased imports from other regions, primarily to the west of PJM,” said Andy Ott, senior vice president of markets.

The annual Reliability Pricing Model auction cleared a record 5,463 MW of new generation and 7,483 MW of imports from outside PJM, nearly double the level of imports from a year ago. Most of the imports — 4,723 MW — came from the Midcontinent Independent System Operator (formerly Midwest ISO).

Demand response contributed 12,408 MW, a reduction from last year, while energy efficiency cleared 1,117 MW, a 21% increase.

Demand Flat

The auction is the first to include the East Kentucky Power Cooperative (EKPC), whose load and resources will be integrated into PJM on June 1, 2013. EKPC’s peak load of 2,200 MW — offset by resources the cooperative owns or controls — pushed PJM’s reliability requirement to 180,332 MW.

But for the addition, PJM’s reliability requirement would have been unchanged from the 2015/16 planning year, and below that for 2014/2015.

Market Mitigation

3-pie-charts-for-cap-mkt-story

As in past auctions, the RTO failed the Three-Pivotal Supplier test for supply-side market power. As a result, prices for all existing generation were limited to the lesser of the supplier’s offer price or approved offer cap.

Gas-fired combustion turbines and combined cycle generators that have not cleared a previous RPM auction were subject to the Minimum Offer Price Rule (MOPR) as a check on buyer-side market power. PJM granted exemptions to the rule for 11,821 MW of “competitive entry” generation — winners of competitive, non-discriminatory requests for proposals open to both new and exist­ing resources — and 1,433 MW of self-supply generation. The exemption procedure was approved by the Federal Energy Regulatory Commission May 2. (See “Split Decision on MOPR.”)  Only 4,915 MW (37%) exempt generation offered cleared.

New Generation

About 82% of capacity offered by new generation units cleared in the total RTO, but its success was highly dependent on geography, with only 27% clearing in EMAAC versus 91% in MAAC.

About 89% of capacity additions for 2016/17 were from natural gas-fired units, mostly combined cycle, with an additional 8% from coal-fired steam units and the remainder from nuclear, diesel and wind.

Imports

Imports offered increased 90%, and virtually all of it cleared. West of PJM imports nearly doubled to 7,081 MW over last year’s auction. MISO offered and cleared 4,723 MW, including generation from areas that will be integrated into MISO by the 2016/2017 Delivery Year. MISO’s installed capacity will increase by more than 37,000 MW with the incorporation of Entergy and South Mississippi Electric Power Association (SME) in December 2013 and Cleco in January 2014.

“It’s really the only forward capacity market available for those regions,” Ott said in a press briefing this morning.

Demand Response Declines

Demand resources offered declined 27% and cleared DR dropped to 12,408 MW, a 16% decrease from a year ago. The biggest declines were in EMAAC and MAAC.

PJM attributed the drop to expectations of decreased prices and the increased scrutiny on DR’s ability to deliver promised resources.

PJM started a stakeholder process in October to standardize the information DR providers must supply to be included in the auction. The initiative was sparked by concern that DR providers might be overestimating or double-counting demand resources. DR offered more than 20% of the forecast peak load in some zones in the 2015/2016 base residual auction.

FERC rejected on procedural grounds rules approved by the Markets and Reliability Committee in March requiring demand response aggregators to provide officer certifications and additional information on their customers. The commission said the changes required amendments to the PJM tariff and thus had to be submitted to FERC for approval. (See “FERC Remands DR Information Requirements.”)

Although the requirements were not officially in effect for this year’s auction, the timing of the commission’s order — coming on April 19, the date DR Plans were due for inclusion in the auction — appeared to have caused more caution in DR providers’ projections.

Energy Efficiency, Renewables Up

While DR was down, energy efficiency offers increased 23% to 1,157 MW, 97% of which cleared.

Contributions from renewable generation also increased, with 871 MW of wind offering and clearing, a 9% increase over last year. Solar generators offered and cleared 90 MW, a 60% increase.

Ott said the increase reflected the rising targets in state energy efficiency and renewable portfolio programs. “It allows customers to monetize their investments,” Ott said.

Gas Continues Growth, Coal Declines

Natural gas-fired generation, which cleared capacity equal to coal for the first time in last year’s auction, cleared almost 65,000 MW this year, while coal’s cleared capacity declined to less than 50,000 MW. About 9,485 MW of coal capacity failed to clear in the auction.

Transmission Constraints Affect Regions

Capacity Auction Clearing Prices by Region 2016/2017 (Note: All Prices Provided in MW-day) (Source: PJM Interconnection, LLC)
Capacity Auction Clearing Prices by Region 2016/2017 (Note: All Prices Provided in MW-day) (Source: PJM Interconnection, LLC)

Clearing prices in the MAAC, ATSI, and PSEG Locational Deliverability Areas (LDA) were higher than in the balance of the RTO due to transmission constraints. Prices for ATSI dropped 68% from last year’s auction, however, due in part to planned transmission improvements to address reliability violations resulting from announced plant retirements.

Historical Role of RPM

PJM credited the Reliability Pricing Model with adding or preserving more than 58,000 MW of capacity in its 10 years of existence.

PJM has added 23,342 MW in installed capacity (ICAP) over that period, including a net increase of 7,858 MW in generation (28,178 MW in new generation, upgrades and reactivations less 20,319 MW in retirements) and 15,483 MW in demand response and energy efficiency.

Over the same period, PJM has gone from a net capacity export of 2,616 MW to net importer of 7,193 MW, a change of 9,809 MW. Canceled plant retirements also contributed 4,640 MW of capacity.

Impact of Environmental Regulations

The 2016/2017 planning year will be subject to the EPA Mercury and Air Toxics Standards (MATS), which are scheduled to take effect in 2015 with a possible one-year compliance extension to April 16, 2016. It also will be subject to the New Jersey High Electricity Demand Day (HEDD) rule, which sets NOx emission rates on intermediate and peaking units effective May 1, 2015.

FERC Orders Rules on Geomagnetic Disturbances

The electric transmission system needs more protections against geomagnetic disturbances like the 1989 solar storm that caused the collapse of the Hydro-Quebec grid, the Federal Energy Regulatory Commission said last week.

In its Final Rule on a Notice of Proposed Rulemaking issued last October (RM12-22),  the commission ordered the North American Electric Reliability Corp. (NERC) to issue standards to close the “reliability gap” regarding geomagnetic disturbances (GMDs) caused by solar events.

1989 Solar Storm (Source: Metatech Corp.)
1989 Solar Storm (Source: Metatech Corp.)

GMDs caused by solar events can cause distortions in the earth’s magnetic field, affecting the operations of pipelines and communications systems as well as electric power systems. Geomagnetically induced currents (GICs) can enter the transmission system, flowing through transformers and transmission lines and leading to increased reactive power consumption and disruptive harmonics that can cause system collapse.

The commission ordered NERC to propose reliability standards in two stages. Stage one standards will mandate operational procedures to mitigate the effect of GMDs. PJM already has GMD operational procedures in place (see below).

A Sense of Urgency

The stage one standards must be submitted for FERC review within about eight months (six months from the effective date of the order, which takes effect 60 days after publication in the Federal Register).

The short deadline underscores the urgency regulators place on preparing for GMDs. The current 11-year solar activity cycle is expected to hit its maximum activity in June. Large solar events often occur within four years of such a cycle maximum, panelists told FERC at a technical conference last year.

In stage two, due within 18 months, NERC must determine what severity GMD will constitute a “benchmark” GMD event. Transmission and generator owners and operators will be required to assess the potential impact of such benchmark events on their equipment and systems.

100-year solar storm: Areas of probable power system collapse; green = transformers; red = population centers. (Source: Oak Ridge National Laboratory)
100-year solar storm: Areas of probable power system collapse; green = transformers; red = population centers. (Source: Oak Ridge National Laboratory)

The severity of GMDs are affected by variables including the strength of the solar event; geology, which affects ground conductivity, and the orientation and length of the transmission lines. If a responsible entity finds no potential GMD impacts in its vulnerability assessment, no additional plan is required.

Entities that are vulnerable will be required to implement protections against “instability, uncontrolled separation, or cascading failures” from such events. Such plans cannot be limited to operational procedures or enhanced training, FERC said.

“These strategies could, for example, include automatically blocking geomagnetically induced currents from entering the Bulk-Power System, instituting specification requirements for new equipment, inventory management, isolating certain equipment that is not cost effective to retrofit, or a combination thereof,” FERC wrote. The commission said it was not ordering NERC to require the use of automatic blocking devices or any specific technology.

Disagreement over Worst-Case Scenario

FERC acknowledged it was acting despite a lack of consensus on the severity of the threat. Some comments on the NOPR supported NERC’s 2012 interim GMD report, which predicted that the worst-case GMD scenario is “voltage instability and subsequent voltage collapse.” Others took side with reports issued in 2010 by the Oak Ridge National Laboratory, which concluded that a severe GMD event could damage or destroy transformers.

FERC said the rule “is warranted by even the lesser consequence of a projected widespread blackout without long-term, significant damage to the Bulk-Power System.”

Damaged Transformer at Salem Nuclear Plant, 1989 (Source: Oak Ridge National Laboratory)
Damaged Transformer at Salem Nuclear Plant, 1989 (Source: Oak Ridge National Laboratory)

The National Academy of Sciences estimated in 2008 that the most extreme solar event could cost more than $1 trillion and require four to 10 years to recover, while the cost of installing protective equipment was estimated at less than 20 cents per year for an average residential customer.

Oak Ridge’s simulation of a 1 in 100-year geomagnetic storm centered over southern Canada predicted that more than 300 EHV transformers would fail or suffer permanent damage, leading to the collapse of the grids serving 130 million people in the Northeast, Mid-Atlantic and Pacific Northwest.

The 1989 incident started shortly before 3 a.m. EST on March 13, when a large impulse in the geomagnetic field was detected near the U.S.-Canada border. That started a series of disturbances that brought down the grid serving Montreal and the rest of Quebec province within about 90 seconds.

The storm also caused large disturbances in the U.S., damaging some transformers severely — including one at the Salem nuclear plant in New Jersey — and nearly knocking out PJM and transmission systems  from New England to the Midwest.

PJM Operating Plans in Place

PJM’s operating plans for dealing with GMDs are detailed in section 3.7 of Manual 13. The plan calls for PJM to notify generation and transmission members via the PJM All-Call system and Emergency Procedure posting application when the National Oceanic and Atmospheric Administration (NOAA) issues an alert for a potential GMD with a ranking of 5 or greater on the 9-point “K-index.”

Once a GMD has been confirmed, PJM dispatchers must operate the system under GMD transfer limits determined from studies that modeled several scenarios, including: loss of the Hydro-Quebec Phase 2 DC line to Sandy Pond; tripping of certain extra high voltage capacitors, and reduction or loss of generation at Artificial Island, the site of the Salem and Hope Creek nuclear plants in New Jersey.

No Guarantees

In its comments in response to the NOPR, PJM said there “is no question that severe space weather has the potential to create serious problems for the Bulk-Power System.” However, PJM and other commenters also asked FERC to clarify that reliability standards cannot eliminate all risks.

The commission agreed: “Given that the scientific understanding of GMDs is still evolving, we recognize that Reliability Standards cannot be expected to protect against all GMD-induced outages.”

Public Interest Orgs. Scold, Praise PJM

By Rich Heidorn Jr.

WHITE SULPHUR SPRINGS, WV — Public interest groups Tuesday scolded PJM for excluding them from the MOPR stakeholder process and for setting its annual meeting at the exclusive Greenbrier resort here.

At their annual meeting with the PJM Board of Managers, the public interest groups and state regulators also praised PJM for its handling of generation retirements and lobbied it to increase use of demand response and energy efficiency.

The meeting included about a dozen representatives from state consumer advocate offices and regulatory commissions as well as several environmental organizations. Others listened via phone.

Robert Mork, attorney in the Indiana Office of Utility Consumer Counselor, said he was able to attend the meeting thanks to funding from the newly formed Consumer Advocates of PJM States (CAPS) because there was no state funding available.  He said the location of the event also created image problems for state officials like him.

While he said the setting “probably isn’t extravagant by private industry standards,” he said the cost and reputation of the Greenbrier — which advertises itself as “one of the finest luxury resorts in the world” — made it difficult for consumer advocates to get approvals to attend.

The Greenbrier
The Greenbrier

Rooms at the hotel cost $315 a night at PJM’s discounted rate. A take-out sandwich set you back $12.

“At the Table”

“I think any concept of RTO inclusiveness needs to have people like us at the table,” Mork said, asking the RTO to consider a less expensive, more accessible location for future meetings.

Board Chairman Howard Schneider told the organizations that the annual meeting with them is important to the board. “Anything we can do to make your job easier, we’re certainly open to suggestions.”

Asked after the meeting whether he had a comment on the criticism of the meeting location, however, Schneider said simply, “no comment.” Would the board discuss the matter later? “I said: `no comment,’” he repeated.

Asked for his response, board member John McNeely Foster reacted like he had been tossed a live grenade: “Nah, I don’t have a comment, sorry.”

Board Member Jean Kinsey was more expansive: “I could have been sympathetic to their plight, but it is what it is,” she said. “Everybody is cost-conscious. But they have smaller resources. I applaud them for doing what they can to get here.”

Room for 500

PJM CEO Terry Boston said PJM staff “will take [the criticism] into consideration for future meetings.”

“There’s very few places in our footprint that can handle our size,” he added, noting that 480 attendees registered.Greenbrier-Interior

Actually, there are more than 50 facilities in the PJM territory with facilities to host 500 people, according to the Cvent Supplier Network, which has an online database. But few of them have a noted golf course like the Greenbrier’s Jack Nicklaus-designed links –- a big draw for the mostly-male attendees at an event that is at least as much social as substantive.

The locations for the next two annual meetings are already set:  next year at the Hyatt Regency in Cambridge, Md., and 2015 at for the Borgati Hotel Casino and Spa in Atlantic City.

Boston added that staff got an “attractive price” for the Greenbrier conference space with a multi-year contract for this year’s event and the one in 2010. He noted that the leisure activities — including free spa treatments and golf — were paid for by sponsors.

The state officials, not allowed to participate in the free activities, were offered a training session Wednesday afternoon instead. Most of them stayed in cheaper lodging off of the resort’s gated grounds.

MOPR Still Rankles

PJM also came under criticism for the stakeholder process that resulted in changes to its minimum offer price rule (MOPR), a tool for preventing buyer-side market power in PJM’s capacity market auctions.

Con­sumer advo­cates and state reg­u­la­tors were out­raged when they learned last September that PJM and the mar­ket mon­i­tor had par­tic­i­pated in con­fi­den­tial set­tle­ment nego­ti­a­tions among seven gen­er­at­ing com­pa­nies and five load-serving enti­ties over more than two months. The result­ing set­tle­ment won an 89% sector-weighted vote.

On May 2, the Fed­eral Energy Reg­u­la­tory Com­mis­sion issued a split decision on the changes, allow­ing the RTO to exempt two cat­e­gories of resources but deny­ing its request to elim­i­nate its cur­rent unit-specific review. FERC rejected state officials’ complaints that the process vio­lated PJM’s Code of Conduct. (See “FERC Upholds PJM Exemptions; Rejects End to Unit-Specific Review.”)

“We felt that the stakeholder discussions were not adequate,” said Bill Fields, an attorney in the Maryland Office of People’s Counsel. “It creates at least an appearance of a lack of independence to announce simultaneously that PJM has a concern about an issue and that a proposed solution to that problem has been agreed to by a group of stakeholders.”

Praise for Staff

The groups praised PJM’s staff for its professionalism and expressed relief that the board had agreed to seek a new three-year contract with Independent Market Monitor Joseph Bowring and his firm Monitoring Analytics.

Attorney Will Burns, who represents environmental groups, praised PJM’s transmission planners for their “herculean job of dealing with a lot of retirements dumped on them all at once.” He also gave PJM credit for its implementation of FERC Order 745 on compensation for demand response and increasing the cap for demand response’s share of the synchronized reserve market from 25% to 33%.

“Thanking PJM is really unlike us,” he said, drawing laughter — a rare light moment in the cordial but tense meeting.

Relief over Market Monitor Contract Extension

The meeting would have been far more contentious had the board not backed off from its original plan to open the monitoring role to competitors.

The board announced last month it was nego­ti­at­ing a new con­tract with the mar­ket mon­i­tor and drop­ping plans to put the con­tract out for bid. The board acted after receiving letters of protest from state reg­u­la­tors, indus­trial con­sumers and coop­er­a­tives, who said the draft request for proposals con­tained terms that would under­mine the inde­pen­dence and qual­ity of the mon­i­tor­ing function. (See “PJM Working on New Deal with Monitor; Backs Down on RFP.”)

“If [a new contract] comes to fruition it will ensure the continued well functioning of the PJM markets,” said Dave Evrard, an attorney in the Pennsylvania Office of Consumer Advocate.

Jackie Roberts, Deputy Consumer Advocate for the West Virginia Public Service Commission, said she was relieved that PJM would not repeat the turmoil of 2007, when Bowring accused PJM’s then-pres­i­dent of attempt­ing to muz­zle him by squelch­ing his reports and cut­ting his budget.

“It was a very difficult time for all of us,” Roberts said. “I think I did a happy dance when I heard [about the board’s decision to extend the contract]. I think we may have avoided some uncertainty in bringing in a new market monitor.”

Environmental Groups Lobby for DR and EE

Environmental groups in attendance pressed their case for energy efficiency and demand response as alternatives to new transmission and generation.

“We believe PJM has an affirmative obligation to identify and evaluate non-transmission alternatives under the Federal Power Act,” said John Moore, senior attorney for the Natural Resources Defense Council’s Sustainable FERC Project.

The Regional Transmission Expansion Plan (RTEP) doesn’t “capture fully all the locational benefits” of non-transmission alternatives, Moore said. “We think waiting for developers to propose these solutions is insufficient.”

Moore said PJM’s requirement that generators provide 90-days notice of plant retirements is too short for energy efficiency and demand response providers to offer alternatives to new transmission lines.

Debate over DR “Saturation”

Environmentalists also said PJM was premature in worrying about the potential for demand response “saturation” – the fear that DR providers will reduce participation as their resources are called on more often.

“We shouldn’t assume there’s a problem until we see some more evidence of it,” said attorney Will Burns.

Board members Sarah Rogers and Ake Almgren insisted their concerns were well founded. “Subscription to DR can fall off and fall off very rapidly,” Rogers said.

Boston said he had seen DR participation decline in Florida. “We found that DR did not stay with us during the boom times” when it was called on more, he said.

Stephen Whitley, president and CEO of the New York ISO, provided his own testimonial in a speech to the Members Committee Thursday. Whitley said New York has lost some of its demand response since calling on those resources five times last year.  “After the fifth time, I got a lot of phone calls from DR participants asking, `What’s going on?’ So that’s a big concern to me.”